1U_Shelf_with_DISTRIBUTION_-_ACE102FALP_01.png
Back to product finder
DC Power - Integrated Shelves

1U Shelf with DISTRIBUTION ACE102FALP

Low Profile Energy System
Contact us

Summary

  • Low profile complete integrated solution
  • Up to 2000W output power
  • Front access modular distribution
  • Battery backup connections and management with integrated LVD
  • Very easy integration in TNM systems
  • Full open interface, ETSI ES 202 336 compliant
  • Easy installation and maintenance

Description

With 2000W output power in a 19" 1U shelf that fits in a 300mm (11,8") deep cabinet, this system is the perfect answer tot he growing number of applications where space is a constraint. This performance is the result of years of experience shared by the engineering teams with their colleagues from field service and operations to design superior power density without any compromise on reliability.
 
Thanks to a full front access distribution, the ACE102FALP allows very easy installation. The shelf does not require any special procedure or tools. The load can be connected on the front panel in a few minutes: no complicated operations or connections to be done on the backside, nothing to knock down! Just mount the shelf and plug it, it is ready to perform!
 
The MCU (Monitoring and Control Unit) supports all the necessary telecom energy monitoring and control functions at the lowest initial investment. It can be upgraded at any time of the life cycle by the features-rich Comp@s card supporting XML, SNMP, FTP and web based services enabling a virtually infinite opportunity to put sites and networks under perfect control.
 
The ACE102FALP features 3 modular distribution units to suit user requirements the best. On top of 4 protected DC output for each of them, the unit can be chosen either with CAN interface, or 6 digital inputs or a protected battery input. Whatever the requirements of your application are, the ACE102FALP has a suitable solution.
 
This solution can be configured to support NiMh batteries from ARTS Energy.

Datasheet

Electrical

  • Input Voltage:
    • Standard AC: 100 to 240Vac
    • Standard DC: 100 to 340Vdc
    • Maximum: 300Vac / 410Vdc
  • Input Frequency: 50/60 Hz
  • Input Current: refer to rectifier module
  • Efficiency: refer to rectifier module
  • Output Power:
    • per rectifier: refer to rectifier module
    • maximum: 2000W
  • Output Load Current (with breaker): 2x10A + 2x16A (front access)
  • Battery breaker: 2x 30A

Mechanical

  • Dimensions:
    • mm: 44H (1U) x 440W x 258D
    • inches: 1.75H x 17.3W x 10.1D
  • Mounting: 19" or ETSI
  • Weight:
    • Shelf: 2.8kg (6,17lb)
    • Rectifier: 1.16kg (2,56lb)
  • Connections
  • Load (protected by breakers): 
    • 2 Positions (30A breakers): Terminal block (4mm²)
    • 2 Positions (10A breakers): Terminal block (1.5 to 4mm²)
  • Battery: 
    • Front -Optional (30A breaker): Terminal block (4mm²)
    • Rear: M5 Stud
  • AC Input: Spring cage terminal block (2 x 2 poles)
  • Alarms (rear): Female 3 x 8 poles connectors
  • CAN communication (Optional): Modular RJ45 connector (8P8C)
  • Digital input (Optional): Modular RJ45 connector (8P8C)

Environmental

  • Temperature:
    • Standard: -20 to 55°C (-4 to 131°F)
    • Extended (de-rated output power): -40 to 70°C (-40 to 158°F)
  • Storage: -40 to 85°C (-40 to 185°F)
  • Humidity:
    • Operating: 20 to 80% RH non-condensing
    • Storage: 10 to 95% RH non-condensing
  • Elevation: Up to 3000m
  • Cooling: Fan cooled (front to rear)

Standards

  • Safety:
    • CE marked
    • EN 62368-1
    • IEC 62368-1 (formerly IEC 60950-1)
    • CEBEC and c-SGS-us markings
  • Environment: RoHS compliant
  • EMC (Residential and Insustrial levels):  
    • EN 61000-6-1
    • ETSI EN300386
    • EN 61000-6-3

Standard Part Numbers

  • 9400 009 00051: ACE102FALP STD1 MCU PRO LCD BAT30A OUT2x10A+2x20A

Related Items

  • DC Power - Rectifiers
  • 1kW Rectifier ECOR1048TN1kW 48V High Performance Rectifier
  • DC Power - DC/DC Converters
  • 1kW DCDC - CDCWI1048TNDC/DC 1000W FR CAR1048TN CDCWI/1048TN
  • Monitoring and Control - MCU
  • MCU0948M41U high Controller for 850W/1000W systems dry alarm only (no comp@s card)

Search for tailor-made solution ?