CAPTIN_1000FA_01.png
Back to product finder
DC Power - Integrated Shelves

CAPTIN 1000FA

Site energy and management solution
Contact us

Summary

  • Full front access design for space restricted enclosures
  • Integrated site management and power feeding
  • Up to 4000W output power
  • 6 protected distribution output
  • Very easy integration in TNM systems
  • Full open interface, ETSI ES 202 336 compliant
  • Battery backup connection and management

Description

The CAPTIN is a total solution designed specifically for use in access network outdoor cabinets and shelters, integrating power supply and management, environmental management, access control and more. Designed in close cooperation with market leading access network operators, it combines redundant power back-up with almost unlimited capabilities for monitoring and control of infrastructure all in a single chassis. Remote communication over IP is provided without the need for any proprietary application or software.
 
 The integration and optimization of site, security and energy management functions into a single power system brings significant savings in terms of module optimization and cabinet cabling. Furthermore, the compact size of the system (266mm deep x 19’’/ETSI wide x 2U (88mm) high) allows a reduction of overall cabinet size when compared to earlier solutions. The modular construction enables progressive investment by installing optional modules in the field at any time.
 
 Reducing the OPEX of our customers is a major objective in the design of Alpha Innovations solutions. Remote monitoring and control of all variables provides advanced knowledge of system status reducing the occurrences of unnecessary site visits. The capabilities of the CAPTIN system far exceed this, supporting additional functions such as statistical data recording and analysis, energy consumption reduction and automatic testing routines - all aimed at reducing network operating expenses.
 
 The integral control module features SNMP and XML standard open architecture. IP based services enable fast and easy transmission of information directly to the appropriate people (security, power, access, etc) as required by the operational organisation of the network.
 
This solution can be configured to support NiMh batteries from ARTS Energy.

Datasheet

Electrical

  • Input Voltage: 90 to 265Vac
  • Input Frequency: 47 to 63Hz
  • Input Current: 20A max with cable on rear side
  • Efficiency: Module up to 95% (ECOR1048TN)
  • Output Voltage: -40.5 to -58Vdc (0V conn. to protective Earth)
  • Output Power: 4000W max (4x 1000W)
  • Output Load Current (with breaker): 4x30A +2x6A
  • Battery Current Breaker: 1x80A
 

Features

  • LVD circuit + Reverse polarity protection
  • Auxiliary Output 12V-1A: with SAM0948
  • Alarms: 4 digital outputs (realays - NO/NC)
  • 2 free digitals inputs
  • 2 digital inputs used for breaker monitoring (Loads, Bat)

Mechanical

  • Dimensions:
    • mm:87H (2U) x 440W x 266D
    • inches:3.5H x 17.3W x 10.5D
  • Mounting:19" or ETSI
  • Weight:
    • Shelf:6.87kg (15.15lb)
    • Rectifier:1.16kg (2.56lb)
  • Connections:
    • Load:
      • 4 Positions:Spring cage terminal block (4 to 6 mm²)
      • 2 Positions:Spring cage terminal block (0.75 to 1 mm²)
    • 12Vdc auxiliary output: Female Jack connector (5.7 x 2.5)
    • Battery: Anderson SB120 connector
    • AC Input: 2 x 2.5mm² (2m single cord)
    • Alarms: Female Sub D15
    • CAN communication (2): Modular RJ45 connector (8P8C)
    • Site Management: See specifications sheet (Optional)

Environmental

  • Temperature: 
    • Standard:-20 to 55°C (-4 to 131°F)
    • Extended (derated output power):-40 to 70°C (-40 to 158°F)
  • Storage:-40 to 85°C (-40 to 185°F)
  • Humidity: 
    • Operating: 20 to 80% RH non-condensing
    • Storage: 10 to 95% RH non-condensing
  • Elevation: Up to 2000m (6562ft)
  • Cooling: Fan cooled (front to rear)

Standards

  • Safety: 
    • CE marked
    • EN60950-1 (CEBEC-SGS marked)
    • Insulation Input-Output: 4242Vdc
    • Insulation Input-Earth: min 2121Vdc
  • Environment: RoHS compliant
  • EMC: see module ECOR1048TN
  • Immunity:  
    • EN61000-4-3 (radiated immunity)
    • EN61000-4-2 (ESD)
    • EN61000-4-6 (conducted immunity)
    • EN61000-4-4 (Burst)
    • EN61000-4-5 (Surge immunity)
    • EN61000-4-11 (Voltage Dips and interrupts)
  • Emission  
    • EN55022 (conducted level B)
    • EN55022 (radiated level B)
    • EN61000-3-2 (Harmonic current)
    • EN61000-3-3 (Voltage fluctuations and flicker)

Standard Part Numbers

  • 9400 002 00051: CAPTIN1000FA STD1 MCU PRO 0.5U SAM READY
  • 9400 002 00052: CAPTIN1000FA STD2 MCU PRO LCD

Related Items

  • Accessories - Connectors And Cables
  • 5304 500 00801LAN Cable
  • 5304 500 0081112V power cable
  • 4004 118 01631Battery wieland connector with 1,2m cable terminated by two ring tongue terminals M6
  • Accessories - Sensors And Actuators
  • 5304 500 00791Temperature Sensor 3m long pigtail
  • 5304 500 00921Temperature probe battery 1,54m with socket to fit in the distribution module or I/O board, ring tongue sensor M6
  • 5304 500 00761RFID KIT Card Reader Genprox-P5
  • 5304 500 00781Water Sensor
  • 5304 500 01031RH sensor for SAM0948 (MOQ: 250pcs)
  • Accessories - Filler
  • Slot Filler ECOR1048Slot Filler for ECOR1048, CAR1048, CAR0948, CAR0548
  • Blind Panel SAMBlind panel to close site slot on CAPTIN300/1000
  • DC Power - Rectifiers
  • ECOR1048TN1kW 48V High Performance Rectifier
  • DC Power - DC/DC Converters
  • CDCWI1048TNDC/DC 1000W FR CAR1048TN CDCWI/1048TN
  • Monitoring and Control - Universal Solutions
  • ADIO DIN 17Extension Module for measuring 10 temperatures (NTC)
  • Monitoring and Control - MCU
  • MCU0948M41U high Controller for 850W/1000W systems dry alarm only (no comp@s card)
  • MCU0948M4LP0,5U high Controller for 850W/1000W systems dry alarms only (no comp@s). Call factory for part number with comp@s
  • Monitoring and Control - Extensions IO
  • SAM0948SITE & ACCESS management card

Search for tailor-made solution ?

Contact us